Anamet Electrical offers several lines of Anaconda SEALTITE suitable for the extreme environments associated with the petrochemical industry.

HTUA: Special PVC cover, Temperature range -51F to +221F (-46C to +105C) HCX: Extreme temperature jacket, Temperature range -76F to +302F (-60C to +150C) EFL: Lightweight corrosion resistant aluminum core, Temperature range -4F to +140F (-20C to +60C) ZHUA: Special Zero Halogen cover, Temperature range -40F to +176F (-40C to +80C) OR: Special Oil Resistant PVC cover, Temperature range -9F to +221F (-23C to +105C)

Type HTUA

UL Listed, CSA Certified Higher and Lower Temperatures Liquid Tight Flexible Metal Conduit (LFMC) Construction

Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance. Durable, sunlight resistant and flame retardant thermoplastic PVC jacket that resists heat, oil and chemical breakdown. Designed for most extreme temperature applications.

NEC Articles Article 250.118 (6) Equipment Grounding Article 300.22 (D) Information Technology Equipment Article 350 Liquid-Tight Flexible Metal Conduit (LFMC) Article 501.10 (B) (2) Class I Div. 2 Article 502.10 (A) (2) and (B) (2) Class II Div. 1 2 Article 503.10 (A) (3) and (B) Class III Div. 1 & 2 Article 620.21 Elevator Wiring Methods Article 645.5 (E) (2) Under Raised Floors

Installation Conduit used with standard liquid-tight connector for easy installation. IP 66/67 Rated when installed with approved connectors. Approved for both exposed and concealed locations Rated for temperature ranges UL temps -51F to + 221F (-46C to +105C), CSA -51F to 167F (-46C to +75C). Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4". Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2. Manufactured in a full range of trade sizes from 3/8" through 4". Approved for direct burial and in concrete trade sizes 3/8" through 4". Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

Type HCX

Extreme Temperature Jacket Liquid Tight Flexible Metal Conduit (LFMC) Construction

Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance. Durable, sunlight resistant thermoplastic rubber jacket that resists heat, oil and chemical breakdown.

Visit link:
Oil and Gas Wiring Conduits